Sign In | Join Free | My himfr.com
Home > Air Cooled Screw Chiller >

100HP Air Cooled Screw Compressor Chiller Industrial chemical chiller For Pvc PE PP Pipe Ex

    Buy cheap 100HP Air Cooled Screw Compressor Chiller Industrial chemical chiller For Pvc PE PP Pipe Ex from wholesalers
     
    Buy cheap 100HP Air Cooled Screw Compressor Chiller Industrial chemical chiller For Pvc PE PP Pipe Ex from wholesalers
    • Buy cheap 100HP Air Cooled Screw Compressor Chiller Industrial chemical chiller For Pvc PE PP Pipe Ex from wholesalers

    100HP Air Cooled Screw Compressor Chiller Industrial chemical chiller For Pvc PE PP Pipe Ex

    Ask Lasest Price
    Brand Name : ANGES
    Model Number : 100HP
    Payment Terms : T/T, L/C
    Delivery Time : 30 days
    • Product Details
    • Company Profile

    100HP Air Cooled Screw Compressor Chiller Industrial chemical chiller For Pvc PE PP Pipe Ex

    100HP Air Cooled Screw Compressor Chiller Industrial chemical chiller 100 Ton Air cooling machine for Pvc PE PP Pipe Extruder.


    An extruder is a plastic molding equipment. Mainly used for various extruded plastic products, such as PE, PP, PVC, ABS, etc. The high temperature generated during the production process will cause difficulty in demoulding and slow molding, so a cooling water system (pool, cooling tower, chiller) is required. Takes away heat from the extruder.


    Model

    Parameter

    AGS-100ASH
    nominal cooling capacitykcal/h281134
    kw326.9
    input powerkw107
    Max. Running currentA243.9
    power supply3PH~380V/50HZ
    refrigeranttypeR22
    refrigerating circuit1
    type of controlthermostatic expansion valve
    compressortypesemi-hermetic screw
    quantity1
    Power89
    start-up modeY-△
    capacity control0-25-50-75-100
    condensertypeair cooled type finned copper tube
    cooling air flow (m3/h)105000
    power(kw)18
    evaporatortypeshell and tube
    quantity1
    chilled fluid flow (m3/h)56.2
    inlet and outlet pipe diameter (inch)4
    safety protectioncompressor over temperature, unit overload, high and low pressure, flow switch, phase sequence, phase-missing, anti-freezing
    net weightkg2860
    Dimensionmm4400*1890*2420

    When the temperature of the chiller is too high, it may be caused by a variety of reasons, which need to be systematically checked and handled. The following are common reasons and solutions for reference:
    Insufficient cooling water flow

    Possible reasons: water pump failure, pipe blockage, dirty filter blockage, valve not fully open.

    Solution:

    Check whether the water pump is operating normally (listen for abnormal sounds, measure current).

    Clean impurities in the filter or pipe.

    Confirm that the valve is fully open.

    Insufficient or leaking refrigerant

    Possible reasons: System leakage leads to reduced refrigerant and reduced cooling efficiency.

    Solution:

    Check the pressure gauge. If the pressure on the low-pressure side is too low, check the leak and add refrigerant (professional operation is required).

    Poor heat dissipation of the condenser

    Possible reasons:

    Air-cooled: dust accumulation on the condenser fins, fan failure or poor environmental ventilation.

    Water-cooled: low cooling tower efficiency and poor water quality lead to scaling.

    Solution:

    Clean the condenser fins or cooling tower fillers.

    Check whether the fan/water pump is normal and improve the ventilation environment.

    Water-cooled type needs to be descaled or replaced regularly.

    Compressor overload or failure

    Possible reasons: unstable power supply voltage, compressor wear, insufficient lubricating oil.

    Solution:

    Check whether the voltage is stable and adjust the power supply line.

    Listen for abnormal noise from the compressor and measure whether the operating current exceeds the limit.

    Contact the manufacturer to repair or replace the compressor.

    Ambient temperature is too high

    Possible reasons: poor ventilation at the installation location of the chiller or the ambient temperature exceeds the design range.

    Solution:

    Add exhaust fans or adjust the location of the equipment to ensure heat dissipation space.

    In high temperature environments, awnings or temporary cooling equipment can be installed.

    Control system failure

    Possible reasons: temperature sensor failure, controller parameter setting error.

    Solution:

    Calibrate or replace the temperature sensor.

    Check the controller setting value (such as target temperature, differential pressure protection value).


    The benefits of using air-cooled chillers:

    1. No cooling towers.
    2. Better environmental stability-no water wastage.
    3. Low maintenance costs.
    4. Easier to operate and control-tower freezing and tower bypass absent.
    5. Chemical costs avoided.
    6. Water costs avoided, especially in cities.






    Quality 100HP Air Cooled Screw Compressor Chiller Industrial chemical chiller For Pvc PE PP Pipe Ex for sale
    Inquiry Cart 0
    Send your message to this supplier
     
    *From:
    *To: Shenzhen Anges Machinery Co., Ltd
    *Subject:
    *Message:
    Characters Remaining: (0/3000)